| Process Conditions | Mass Flux Theory Outputs | CFD Outputs | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Case | Inlet Q, m3/hr | Effluent Q, m3/hr | RAS Q, m3/hr | Recycle ratio | Inlet MLSS, mg/L | SSVI, mL/g | Flux relationship | RAS conc., kg/m3 | Crit. I(a), % (Act/Max) | Crit. I(b), % (Act/Max) | Crit. II, % (Act/Max) | Crit. III, % (Act/Max) | Crit. IV, m3/h.m | ESS, mg/L | Bed Depth, m |
| Case4 | 1020.000 | 600.000 | 420.000 | 0.7000 | 3000 | 120 | Pitman & White |
7.3 | 80.2 | 90.4 | 75.5 | 81.5 | 6.37 | 20 | 1.90 |
| Case1 | 510.000 | 300.000 | 210.000 | 0.7000 | 3000 | 100 | Pitman & White |
7.3 | 55.8 | 37.0 | 26.2 | 34.0 | 3.18 | 14 | 2.99 |
| Case2 | 510.000 | 300.000 | 210.000 | 0.7000 | 3000 | 120 | Pitman & White |
7.3 | 64.2 | 45.2 | 37.8 | 40.7 | 3.18 | 15 | 2.80 |
| Case5 | 1056.000 | 660.000 | 396.000 | 0.6000 | 3500 | 125 | Pitman & White |
9.3 | 104.0 | 89.8 | 117.2 | 108.9 | 7.0 | 64 | 0.26 |
| Case3 | 850.000 | 500.000 | 350.000 | 0.7000 | 3000 | 120 | Pitman & White |
7.3 | 75.7 | 75.3 | 62.9 | 67.9 | 5.31 | 18 | 2.34 |